Nesteknik Preloader
nesteknik logo
Monday - Friday 09:00 - 17:00

As Nesteknik, our mission is to develop sustainable and efficient technologies with innovative engineering solutions.

Contact Us Nesteknik Kimya San. ve Tic. Ltd. Şti.
Karslılar Mh. 82033 Sk. No: 9 Çukurova/ADANA/TURKEY
+90 322 233 46 93 info@nesteknik.com
FS10i Flow Switch + Monitor

Category

Brand

Fluid Components International (FCI) Fluid Components International (FCI)

Product Code: FS10i Series

Get Product Information

TEKLİF İSTEYİN

FS10i Flow Switch + Monitor Details

  • Materials of Construction (Wetted Parts)

316L SS with Hastelloy C-22 thermowells
 

  • Flow Sensitivity/Setpoint Range

Water:    0.01 FPS to 0.5 FPS [0,003 MPS to 0,15 MPS]
Air/Gas: 0.25 FPS to 400 SFPS [0,076 MPS to 122 MPS]
 

  • Repeatability: ±0.5% of reading

 

  • Temperature Coefficient For temperatures > ±30°F [±16°C]

Gas: Maximum ±0.025% of reading/°F up to 250°F [±0,05% of reading/°C up to 121°C]
Liquid: Maximum ±0.2% of reading/°F up to 250°F [±0,367% of reading/°C up to 121°C]
 

  • Operating Temperature

-40°F to 250°F [-40°C to 121]
Teflon ferrule maximum temperature is 200°F [93°C]
 

  • Operating Pressure

2000 psi [138 bar]
Teflon ferrule maximum pressure is 150 psig [10 bar(g)]
 

  • Insertion “U” lengths

2″[50 mm] fixed
6″[150 mm] with variable insertion depth, compression fitting with Teflon or metal ferrule
 

Electronics

 

  • Display

10 segment LED array, sequential lighting related to flow rate and flashing when trip point exceeded
 

  • Output Signals

Relay: SPDT, 1A @ 24 Vdc, 120 Vac Analog: 4-20 mA trending*
Serial: RS232C I/O
*500 ohm maximum load; user scalable, general purpose, uncalibrated output proportional to flow rate for trend monitoring or assignable to temperature; fault indication per NAMUR NE43 guidelines, user-selectable for high (>21.0mA) or low (<3.6mA) default
For linearized and calibrated analog outputs, see FCI’s line of thermal mass flow meter products
 

  • Operation

Two top-mounted buttons to program switch/trip point, zero and span setting, fail-safe, relay hysterisis and relay time delay; button operation may be user disabled to prevent unwanted changes; all set-up function are also user programmable via the RS232C serial port
 

  • Trip Point Hysteresis Control: 0-100% of span

 

  • Trip Point Time Delay: user settable for 0-65,000 seconds

 

  • Input Power

 24 Vdc (21.5 Vdc to 30Vdc); 2.5 watts maximum
 

  • Operating Temperature

 -40°C to 160°F [-40°C to 71°C]
 

Enclosure/Housing

 

  • Material: stainless steel body; aluminum end-cap/top with polyester overlay and clear, silicone sheath impact guard

 

  • Protection Rating:

​Non-Ex Installations:      IP65 IP66, IP67
FM, FMc approved:         NEMA 4X
ATEX, IECEx approved:   IP64
 

Agency Approvals

  • FM, FMc:  Nonincendive, Class I, Division 2, Groups A,B,C,D; Class II, Division 2, Groups E,F,G; Class III, T4@Ta=71°C, Type 4X

  • ATEX, IECEx:  Nonincendive for gas and dust, Zone 2; II 3 G Ex ec IIC T4 Gc;  II 3 D Ex tc IIIC T81°C Dc; IP64

  • EAC/TR CU:  Pending. Contact FCI

  • Other CE Mark, CRN, complies with Canadian electrical code requirement of ANSI/ISA 12.27.01-2011 as single seal device.

  • IEC 61508 (SIL):  SIL 2 Compliant, SFF 90%

Would you like to know more about this product?

TEKLİF İSTEYİN